Moisture Load and Dehumidifier Capacity Calculator
Model a daily moisture mass balance from dry-air flow and humidity ratios, then compare assessed removal needs with documented equipment capacity.
Use this result well
- Inputs that matter
- Dry-air mass flow (kg dry air/h), Inlet humidity ratio (kg water/kg dry air), Target humidity ratio (kg water/kg dry air), Daily flow operating hours, and 8 more
- Output to expect
- Daily moisture mass balance, Dehumidifier capacity and runtime check
- Check the units and required inputs before comparing results.
- Keep the assumptions with a copied result so you can reproduce the calculation later.
Related Tools
Tools you might need next
Calculate service dates from documented intervals or compare actual runtime readings with a service threshold, then save and export the record.
Build an installed quote, compare lifetime costs and calculate material packs. Separate payment-day cash from later reimbursements using your project records.
Compare documented total and sensible cooling loads with matched equipment capacities and show the implied latent differences.
Reference & details
How it works
Updated September 2026
How it works
Updated September 2026Daily moisture mass balance
Estimate one day's ongoing moisture balance from a documented dry-air mass flow, inlet and target humidity ratios, operating hours and separately estimated internal/other moisture sources. Humidity ratio is kilograms of water per kilogram of dry air; a relative-humidity percentage is not an interchangeable input.
Net kg/day = dry-air kg/h × (inlet − target humidity ratio) × hours/day + internal kg/day + other kg/day; required removal = max(0, net).Dehumidifier capacity and runtime check
Compare a separately established daily moisture-removal need with equipment performance at matching temperature and humidity. Enter a documented 24-hour removal rate and your available operating hours. The runtime scaling assumes that rate can be sustained while operating.
Available L/day = stated 24-hour capacity × unit factor × operating hours ÷ 24; difference = available − required.Updated: September 2026
Example Scenarios
The built-in example is an arithmetic illustration. Replace it with your own verified measurements or planning assumptions.
→ 10.64 kg/day modeled moisture removal
The built-in example is an arithmetic illustration. Replace it with your own verified measurements or planning assumptions.
→ 1.36 L/day capacity difference
FAQ
About Moisture Load and Dehumidifier Capacity Calculator
Estimate one day's ongoing moisture balance from a documented dry-air mass flow, inlet and target humidity ratios, operating hours and separately estimated internal/other moisture sources. Humidity ratio is kilograms of water per kilogram of dry air; a relative-humidity percentage is not an interchangeable input. Compare a separately established daily moisture-removal need with equipment performance at matching temperature and humidity. Enter a documented 24-hour removal rate and your available operating hours. The runtime scaling assumes that rate can be sustained while operating.